HomeMy WebLinkAbout078413 - penetration firestopping.pdfUNC-CH Carolina Union UNC02.12 September 07, 2018 Auditorium Renovation SCO ID# 17-18066-01A Bid Set Chapel Hill, North Carolina PENETRATION FIRESTOPPING 07 84 13 - 1 SECTION 07 84 13 - PENETRATION FIRESTOPPING PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Penetrations in fire-resistance-rated walls. 1.02 ACTION SUBMITTALS A. Product Data: For each type of product. B. Product Schedule: For each penetration firestopping system. Include locatio n, illustration of firestopping system, and design designation of qualified testing and inspecting agency. 1.03 INFORMATIONAL SUBMITTALS A. Qualification Data: For Installer. B. Product Test Reports: For each penetration firestopping system, for tests performed by a qualified testing agency. 1.04 CLOSEOUT SUBMITTALS A. Installer Certificates: From Installer indicating that penetration firestopping systems have been installed in compliance with requirements and manufacturer's written instructions. 1.05 QUALITY ASSURANCE A. Installer Qualifications: A firm that has been approved by FM Global according to FM Global 4991, "Approval of Firestop Contractors," or been evaluated by UL and found to comply with its "Qualified Firestop Contractor Program Requirements." 1.06 PROJECT CONDITIONS A. Environmental Limitations: Do not install penetration firestopping system when ambient or substrate temperatures are outside limits permitted by penetration firestopping system manufacturers or when substrates are wet because of rain, frost, condensation, or other causes. B. Install and cure penetration firestopping materials per manufacturer's written instructions using natural means of ventilations or, where this is inadequate, forced-air circulation. 1.07 COORDINATION A. Coordinate construction of openings and penetrating items to ensure that penetration firestopping systems can be installed according to specified firestopping system design. B. Coordinate sizing of sleeves, openings, core-drilled holes, or cut openings to accommodate penetration firestopping systems. UNC-CH Carolina Union UNC02.12 September 07, 2018 Auditorium Renovation SCO ID# 17-18066-01A Bid Set Chapel Hill, North Carolina PENETRATION FIRESTOPPING 07 84 13 - 2 PART 2 - PRODUCTS 2.01 PERFORMANCE REQUIREMENTS A. Fire-Test-Response Characteristics: 1. Perform penetration firestopping system tests by a qualified testing agency acceptable to authorities having jurisdiction. 2. Test per testing standards referenced in "Penetration Firestopping Systems" Article. Provide rated systems complying with the following requirements: a. Penetration firestopping systems shall bear classification marking of a qualified testing agency. 1) UL in its "Fire Resistance Directory." 2) Intertek Group in its "Directory of Listed Building Products." 3) FM Global in its "Building Materials Approval Guide." 2.02 PENETRATION FIRESTOPPING SYSTEMS A. Penetration Firestopping Systems: Systems that resist spread of fire, passage of smoke and other gases, and maintain original fire-resistance rating of construction penetrated. Penetration firestopping systems shall be compatible with one another, with the substrates forming openings, and with penetrating items if any. 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. 3M Fire Protection Products. b. A/D Fire Protection Systems Inc. c. Grabber Construction Products. d. Hilti, Inc. e. NUCO Inc. f. RectorSeal. g. Specified Technologies, Inc. h. Tremco, Inc. B. Penetrations in Fire-Resistance-Rated Walls: Penetration firestopping systems with ratings determined per ASTM E 814 or UL 1479, based on testing at a positive pressure differential of 0.01-inch wg. 1. F-Rating: Not less than the fire-resistance rating of constructions penetrated. C. Exposed Penetration Firestopping Systems: Flame-spread and smoke-developed indexes of less than 25 and 450, respectively, per ASTM E 84. D. Accessories: Provide components for each penetration firestopping system that are needed to install fill materials and to maintain ratings required. Use only those components specified by penetration firestopping system manufacturer and approved by qualified testing and inspecting agency for conditions indicated. 1. Permanent forming/damming/backing materials. 2. Substrate primers. 3. Collars. 4. Steel sleeves. UNC-CH Carolina Union UNC02.12 September 07, 2018 Auditorium Renovation SCO ID# 17-18066-01A Bid Set Chapel Hill, North Carolina PENETRATION FIRESTOPPING 07 84 13 - 3 2.03 FILL MATERIALS A. Latex Sealants: Single-component latex formulations that do not re-emulsify after cure during exposure to moisture. B. Firestop Devices: Factory-assembled collars formed from galvanized steel and lined with intumescent material sized to fit specific diameter of penetrant. C. Intumescent Composite Sheets: Rigid panels consisting of aluminum-foil-faced intumescent elastomeric sheet bonded to galvanized-steel sheet. D. Intumescent Putties: Nonhardening, water-resistant, intumescent putties containing no solvents or inorganic fibers. E. Intumescent Wrap Strips: Single-component intumescent elastomeric sheets with aluminum foil on one side. F. Mortars: Prepackaged dry mixes consisting of a blend of inorganic binders, hydraulic cement, fillers and lightweight aggregate formulated for mixing with water at Project site to form a nonshrinking, homogeneous mortar. G. Pillows/Bags: Reusable heat-expanding pillows/bags consisting of glass-fiber cloth cases filled with a combination of mineral-fiber, water-insoluble expansion agents, and fire-retardant additives. Where exposed, cover openings with steel-reinforcing wire mesh to protect pillows/bags from being easily removed. H. Silicone Foams: Multicomponent, silicone-based liquid elastomers that, when mixed, expand and cure in place to produce a flexible, nonshrinking foam. I. Silicone Sealants: Single-component, silicone-based, neutral-curing elastomeric sealants. 2.04 MIXING A. Penetration Firestopping Materials: For those products requiring mixing before application, comply with penetration firestopping system manufacturer's written instructions for accurate proportioning of materials, water (if required), type of mixing equipment, selection of mixer speeds, mixing containers, mixing time, and other items or procedures needed to produce products of uniform quality with optimum performance characteristics for application indicated. PART 3 - EXECUTION 3.01 EXAMINATION A. Examine substrates and conditions, with Installer present, for compliance with requirements for opening configurations, penetrating items, substrates, and other conditions affecting performance of the Work. B. Proceed with installation only after unsatisfactory conditions have been corrected. UNC-CH Carolina Union UNC02.12 September 07, 2018 Auditorium Renovation SCO ID# 17-18066-01A Bid Set Chapel Hill, North Carolina PENETRATION FIRESTOPPING 07 84 13 - 4 3.02 PREPARATION A. Surface Cleaning: Before installing penetration firestopping systems, clean out openings immediately to comply with manufacturer's written instructions and with the following requirements: 1. Remove from surfaces of opening substrates and from penetrating items foreign materials that could interfere with adhesion of penetration firestopping materials. 2. Clean opening substrates and penetrating items to produce clean, sound surfaces capable of developing optimum bond with penetration firestopping materials. Remove loose particles remaining from cleaning operation. 3. Remove laitance and form-release agents from concrete. B. Prime substrates where recommended in writing by manufacturer using that manufacturer's recommended products and methods. Confine primers to areas of bond; do not allow spillage and migration onto exposed surfaces. 3.03 INSTALLATION A. General: Install penetration firestopping systems to comply with manufacturer's written installation instructions and published drawings for products and applications. B. Install forming materials and other accessories of types required to support fill materials during their application and in the position needed to produce cross-sectional shapes and depths required to achieve fire ratings. 1. After installing fill materials and allowing them to fully cure, remove combustible forming materials and other accessories not forming permanent components of firestopping. C. Install fill materials by proven techniques to produce the following results: 1. Fill voids and cavities formed by openings, forming materials, accessories and penetrating items to achieve required fire-resistance ratings. 2. Apply materials so they contact and adhere to substrates formed by openings and penetrating items. 3. For fill materials that will remain exposed after completing the Work, finish to produce smooth, uniform surfaces that are flush with adjoining finishes. 3.04 IDENTIFICATION A. Wall Identification: Permanently label walls containing penetration firestopping systems with the words "FIRE AND/OR SMOKE BARRIER - PROTECT ALL OPENINGS," using lettering not less than 3 inches high and with minimum 0.375-inch strokes. 1. Locate in accessible concealed floor, floor-ceiling, or attic space at 15 feet from end of wall and at intervals not exceeding 30 feet. B. Penetration Identification: Identify each penetration firestopping system with legible metal or plastic labels. Attach labels permanently to surfaces adjacent to and within 6 inches of penetration firestopping system edge so labels are visible to anyone seeking to remove penetrating items or firestopping systems. Use mechanical fasteners or self-adhering-type labels with adhesives capable of permanently bonding labels to surfaces on which labels are placed. Include the following information on labels: UNC-CH Carolina Union UNC02.12 September 07, 2018 Auditorium Renovation SCO ID# 17-18066-01A Bid Set Chapel Hill, North Carolina PENETRATION FIRESTOPPING 07 84 13 - 5 1. The words "Warning - Penetration Firestopping - Do Not Disturb. Notify Building Management of Any Damage." 2. Contractor's name, address, and phone number. 3. Designation of applicable testing and inspecting agency. 4. Date of installation. 5. Manufacturer's name. 6. Installer's name. 3.05 FIELD QUALITY CONTROL A. Owner will engage a qualified testing agency to perform tests and inspections according to ASTM E 2174. B. Where deficiencies are found or penetration firestopping system is damaged or removed because of testing, repair or replace penetration firestopping system to comply with requirements. C. Proceed with enclosing penetration firestopping systems with other construction only after inspection reports are issued and installations comply with requirements. 3.06 CLEANING AND PROTECTION A. Clean off excess fill materials adjacent to openings as the Work progresses by methods and with cleaning materials that are approved in writing by penetration firestopping system manufacturers and that do not damage materials in which openings occur. B. Provide final protection and maintain conditions during and after installation that ensure that penetration firestopping systems are without damage or deterioration at time of Final Acceptance. If, despite such protection, damage or deterioration occurs, immediately cut out and remove damaged or deteriorated penetration firestopping material and install new materials to produce systems complying with specified requirements. END OF SECTION 07 84 13