HomeMy WebLinkAbout1_G002 - NCSBC APPENDIX B - BUILDING CODE SUMMARY.pdfSpecial Uses:402 403 404 405 406 407 408 409 410 411 412
414 415 416 417 418 419 420 421 422 423 424413
426 427425
Special Provisions:509.2 509.3 509.4 509.5 509.6 509.7 509.8 509.9
Mixed Occupancy:No Yes Separation: Hr. Exception:
Incidental Use Separation (508.2.5)
This separation is not exempt as a Non-Separated Use (see exceptions).
Non-Separated Use (508.3)
The required type of construction for the building shall be determined by applying the height and area limitations
for each of the applicable occupancies to the entire building. The most restrictive type of construction, so
determined, shall apply to the entire building.
Separated Use (508.4) - See below for area calculations
For each story, the area of the occupancy shall be such that the sum of the ratios of the actual floor area of each use
divided by the allowable floor area for each use shall not exceed 1.
Actual Area of Occupancy A
Allowable Area of Occupancy A
+
Actual Area of Occupancy B
Allowable Area of Occupancy B
< 1
+=< 1.00
STORY
NO.
DESCRIPTION
AND USE
(A)
BLDG AREA
PER STORY
(ACTUAL)
(C)
AREA FOR
FRONTAGE
INCREASE1
(D)
AREA FOR
SPRINKLER
INCREASE2
(E)
ALLOWABLE
AREA OR
UNLIMITED3
(F)
MAXIMUM
BUILDING
AREA4
(B)
TABLE 503
AREA
5
1.00
X
100
200
100
200
Occupancy:
ALLOWABLE AREA
Assembly
Business
Educational
Factory
Hazardous
Institutional
I-3 Condition
Mercantile
Residential
Storage
Utility and Miscellaneous
A-1 A-2 A-3 A-4 A-5
F-1 Moderate F-2 Low
H-1 Detonate H-2 Deflagrate H-3 Combust H-4 Health H-5 HPM
I-1 I-2 I-3 I-4
12345
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High Piled
Parking Garage Open Repair GarageEnclosed
Accessory Occupancies:
Assembly
Business
Educational
Factory
Hazardous
Institutional
I-3 Condition
Mercantile
Residential
Storage
Utility and Miscellaneous
A-1 A-2 A-3 A-4 A-5
F-1 Moderate F-2 Low
H-1 Detonate H-2 Deflagrate H-3 Combust H-4 Health
I-1 I-2 I-3 I-4
12345
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High Piled
Parking Garage Open Repair GarageEnclosed
H-5 HPM
Incidental Uses (Table 508.2.5) :
Furnace room where any piece of equipment is over 400,000 Btu per hour input
Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower
Refrigerant machine room
Hydrogen cutoff rooms, not classified as Group H
Incinerator rooms
Paint shops, not classified as Group H, located in occupancies other than Group F
Laboratories and vocational shops, not classified as Group H. located in a Group E or I-2 occupancy
Laundry rooms over 100 square feet
Group I-3 cells equipped with padded surfaces
Group I-2 waste and linen collection rooms
Waste and linen collection rooms over 100 square feet
Stationary storage battery systems having a liquid electrolyte capacity of more than 50 gallons, or a lithium-ion
capacity of 1,000 pounds used for facility standby power, emergency power or uninterrupted power supplies
Rooms containing fire pumps
Group I-2 storage rooms over 100 square feet
Group I-2 commercial kitchens
Group I-2 laundries equal to or less than 100 square feet
Group I-2 rooms or spaces that contain fuel-fired heating equipment
X
X
X
2012 APPENDIX B
BUILDING CODE SUMMARY
FOR ALL COMMERCIAL PROJECTS
Name of Project:
Address:Zip Code:
Proposed Use:
Owner/Authorized Agent: Phone: E-Mail:
Owned By: City/County Private State
Code Enforcement Jurisdiction: City: County: State
LEAD DESIGN PROFESSIONAL:
DESIGNER
Architectural
Civil
Electrical
Fire Alarm
Plumbing
Mechanical
Sprinkler-Standpipe
Structural
Retaining Walls>5' High
Other
FIRM NAME LICENSE # TELEPHONE E-MAIL
2012 EDITION OF CODE FOR:New Construction Addition Upfit
Alteration Repair RenovationEXISTING:Reconstruction
CONSTRUCTED:(date)
RENOVATED:(date)
ORIGINAL USE(S)(Ch. 3) :
CURRENT USE(S)(Ch. 3) :
PROPOSED USE(S)(Ch. 3) :
BASIC BUILDING DATA
Construction Type:
(check all that apply)
I-A V-AIV-AIII-AII-A
I-B V-BIII-BII-B
Sprinklers:No Partial Yes NFPA 13 NFPA 13R NFPA 13D
Standpipes:No Yes Class I II III Wet Dry
Fire District:No Yes (Primary)Flood Hazard Area:No Yes
Building Height: (feet)
Gross Building Area:
FLOOR EXISTING (SF) NEW (SF) SUB-TOTAL (SF)
TOTAL
(EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)
120,505 SF
MACNIDER HALL 3RD FLOOR RENOVATIONS
MACNIDER HALL, UNIVERSITY OF NORTH CAROLINA AT CHAPEL HILL 27599
BUSINESS
LUKE O. HOFF, PE LHOFF@FAC.UNC.EDU
X
BJAC PA Jennifer Amster 7475 919-645-3216 jennifer@bjac.com
N/A
Sigma
Sigma
Sigma
N/A
N/A
N/A
X
X
1950
UNKNOWN
LAB, OFFICE
OFFICE
LAB, OFFICE
X
X
X
XX
69'-0"
120,505 SF 0 SF
X
ALLOWABLE HEIGHT
ALLOWABLE
(TABLE 503)
Type of Construction
Building Height in Feet
Building Height in Stories
INCREASE FOR SPRINKLERS SHOWN ON PLANS CODE
REFERENCE
Type
Feet = H + 20' =
Stories + 1 =
I-B
160' - 0"
11
160' - 0"
11
I-B
69' - 0"
6
TABLE 503
TABLE 503
TABLE 503
Frontage area increase from Section 506.2 are computed thus:
Unlimited area applicable under conditions of Sections Group B, F, M, S, A-4 (507);
Group A motion picture (507.10); Malls (402.6); and H-2 Aircraft Hangers (507.8)
Maximum Building Area = total number of stories in the building x E (506.4)
The maximum area of parking garages must comply with 406.3.5. The maximum area
of air traffic control towers must comply with 412.1.2.
The Sprinkler increase per Section 506.3 is as follows:
1
2
3
4
5
a. Multi-story building Is = 200 % = 7.5
b. Single-story building Is = 300 % = 5
c. Ratio (F/P) = 1 (F/P)
e. Percent of frontage increase I = 100 [F/P -0.25] x W/30 = 2.5 (%)
a. Perimeter which fronts a public way or open space having 20 feet minimum
width = 1 (F)b. Total Building Perimeter = 1 (P)
d. W = Minimum width of public way = 1 (W)
FIRE PROTECTION REQUIREMENTS
BUILDING ELEMENT FIRE
SEPARATION
DISTANCE
(FEET)
RATING
REQ'D PROVIDED
(W/ *
REDUCTION)
DETAIL #
AND
SHEET #
DESIGN #
FOR
RATED
ASSEMBLY
DESIGN # FOR
RATED
PENETRATION
DESIGN #
FOR
RATED
JOINTS
Structural Frame,
including columns,
girders, trusses
Bearing Walls
Exterior
North
East
West
South
Interior
Nonbearing Walls and
Partitions
Exterior Walls
North
East
West
South
Interior Walls and
Partitions
Floor Construction
Including Supporting
Beams and Joists
Roof Construction
Including Supporting
Beams and Joists
Shaft Enclosures - Exit
Shaft Enclosures -
Other
Corridor Separation
Occupancy Separation
Party/Fire Wall
Separation
Smoke Barrier
Separation
Tenant Separation
Incidental Use
Separation
* Indicate section number permitting reduction
2 EXISTING
2 EXISTING
NA
NA
NA
NA
2 EXISTING
NA
NA
NA
NA
00
2 EXISTING
1 EXISTING
2 EXISTING
2 EXISTING
0*
N/A
1 EXISTING
Emergency Lighting:
LIFE SAFETY SYSTEM REQUIREMENTS
No Yes
Exit Signs: No Yes
Fire Alarm: No Yes
Smoke Detection Systems: No Yes
Panic Hardware: No Yes
Partial
X
X
X
X
X
LIFE SAFETY PLAN REQUIREMENTS
Life Safety Plan Sheet #:
Fire and/or smoke rated wall locations (Chapter 7)
Assumed and real property line locations
Exterior wall opening area with respect to distance to assumed property lines (705.8)
Existing structures within 30’ of the proposed building
Occupancy types for each area as it relates to occupant load calculation (Table 1004.1.1)
Occupant loads for each area
Exit access travel distances (1016)
Common path of travel distances (1014.3 & 1028.8)
Dead end lengths (1018.4)
Clear exit widths for each exit door
Maximum calculated occupant load capacity each exit door can accommodate based on egress width (1005.1)
Actual occupant load for each exit door
A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for purposes of
occupancy separation
Location of doors with panic hardware (1008.1.10)
Location of doors with delayed egress locks and the amount of delay (1008.1.9.7)
Location of doors with electromagnetic egress locks (1008.1.9.8)
Location of doors equipped with hold-open devices
Location of emergency escape windows (1029)
The square footage of each fire area (902)
The square footage of each smoke compartment (407.4)
Note any code exceptions or table notes that may have been utilized regarding the items above
G101
X
X
X
X
X
X
X
X
X
X
X
ACCESSIBLE DWELLING UNITS
(SECTION 1107)
TOTAL
UNITS
ACCESSIBLE
UNITS
REQUIRED
ACCESSIBLE
UNITS
PROVIDED
TYPE A
UNITS
PROVIDED
TYPE B
UNITS
REQUIRED
TYPE B
UNITS
PROVIDED
TOTAL
ACCESSIBLE
UNITS PROVIDED
TYPE A
UNITS
REQUIRED
ACCESSIBLE PARKING
(SECTION 1106)
LOT OR PARKING
AREA
TOTAL # OF PARKING SPACES
REQUIRED PROVIDED
# OF ACCESSIBLE SPACES PROVIDED
REGULAR WITH
5' ACCESS
AISLE
VAN SPACES WITH
132" ACCESS
AISLE
8' ACCESS
AISLE
TOTAL #
ACCESSIBLE
PROVIDED
000000
TOTAL 0 0 0 0 0 0
DESIGN LOADS:
STRUCTURAL DESIGN
Importance Factors:Wind (I )
Snow (I )
Seismic (I )
W
S
E
Live Loads:Roof
Mezzanine
Floor
psf
psf
psf
Ground Snow Load:psf
Wind Load:Basic Wind Speed
Exposure Category
Wind Base Shears (for MWFRS)
mph (ASCE-7)
Vx = Vy =
SEISMIC DESIGN CATEGORY:
Provide the following Seismic Design Parameters:
ABCD
Occupancy Category (Table 1604.5) I II III IV
Spectral Response Acceleration SS %g S
I %g
Site Classification (Table 1613.5.2) A B C D E F
Data Source: Field Test Presumptive Historical Data
Basic Structural System (check one)
Bearing Wall
Building Frame
Moment Frame
Dual w/ Special Moment Frame
Dual w/ Intermediate R/C or Special Steel
Inverted Pendulum
Seismic Base Shear:Vx = Vy =
Analysis Procedure:Simplified Equivalent Lateral Force Dynamic
Architectural, Mechanical Components Anchored?:Yes No
LATERAL DESIGN CONTROL:Earthquake Wind
SOIL BEARING CAPACITIES:
Field Test (provide copy of test report)
Presumptive Bearing Capacity
Pile Size, Type, and Capacity
psf
psf
SPECIAL INSPECTIONS REQUIRED:Yes No
PLUMBING FIXTURE REQUIREMENTS
(TABLE 2902.1)
USE WATERCLOSETS
MALE FEMALE
URINALS LAVATORIES
MALE FEMALE REGULAR ACCESSIBLE
SHOWERS/
TUBS
DRINKING FOUNTAINS
EXISTING
NEW
REQUIRED
SPACE
Special Approval: (Local Jurisdiction, Department of Insurance, OSC, DPI, DHHS, ICC, etc., describe below)
SPECIAL APPROVALS
OFFICE OF STATE CONSTRUCTION
ENERGY REQUIREMENTS:
ENERGY SUMMARY
The following data shall be considered minimum and any special attribute required to meet the energy code shall also be
provided. Each Designer shall furnish the required portions of the project information for the plan data sheet. If performance
method, state the annual energy cost for the standard reference design vs annual energy cost for the proposed design.
Climate Zone:345
Method of Complaine:
Prescriptive (Energy Code)
Performance (Energy Code)
Prescriptive (ASHRAE 90.1)
Performance (ASHRAE 90.1)
THERMAL ENVELOPE
Roof/Ceiling Assembly (each assembly)
Description of Assembly:
U-Value of Assembly:
R-Value of Insulation:
Skylights in Each Assembly:
U-Value of Skylight:
Total Square Footage of Skylights in Each Assembly:
Exterior Walls (each assembly)
Description of Assembly:
U-Value of Assembly:
R-Value of Insulation:
Openings (Windows or Doors With Glazing
U-Value of Assembly:
Solar Heat Gain Coefficient:
Projection Factor:
Door R-Value:
Walls Below Grade (each assembly)
Description of Assembly:
U-Value of Assembly:
R-Value of Insulation:
Floors Over Unconditioned Space (each assembly)
Description of Assembly:
U-Value of Assembly:
R-Value of Insulation:
Floors Slab On Grade
Description of Assembly:
U-Value of Total Assembly:
R-Value of Insulation:
Horizontal/Vertical Requirement:
Slab Heated:
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
MECHANICAL SUMMARY
Thermal Zone
Winter Dry Bulb:
Summer Dry Bulb:
Interior Design Conditions
Winter Dry Bulb:
Summer Dry Bulb:
Relative Humidity:
Building Heating Load:
Building Cooling Load:
Mechanical Spacing Conditioning System
Unitary
Description of Unit
Heating Efficiency:
Cooling Efficiency
Size Category of Unit:
Boiler
Size Category. If oversized, state reason:
Chiller
Size Category. If oversized, state reason:
List Equipment Efficiencies:
ELECTRICAL SYSTEM AND EQUIPMENT
ELECTRICAL SUMMARY
Method of Compliance:
Energy Code:
ASHRAE 90.1:
Prescriptive Performance
Prescriptive Performance
Lighting Schedule (each fixture type)
lamp type required in fixture
number of lamps in fixture
ballast type used in the fixture
number of ballasts in fixture
total wattage per fixture
total interior wattage specified vs. allowed (whole building or space by space)
total exterior wattage specified vs. allowed
Additional Prescriptive Compliance
506.2.1 More Efficient Mechanical Equipment
506.2.2 Reduced Lighting Power Density
506.2.3 Energy Recovery Ventilation Systems
506.2.4 Higher Efficiency Service Water Heating
506.2.5 On-Site Supply of Renewable Energy
506.2.6 Automatic Daylighting Control Systems
22,530 SF4TH 22,530 SF 0 SF
22,530 SF3RD 22,530 SF 0 SF
22,530 SF2ND 22,530 SF 0 SF
22,530 SF1ST 22,530 SF 0 SF
22,530 SFGROUND 22,530 SF 0 SF
7,855 SFBASEMENT 7,855 SF 0 SF
CORRIDOR RATING NOT REQUIRED IN SINGLE TENANT BUILDING PER NC BUILDING CODE TABLE 1018.1
FOOTNOTE 'F' BUSINESS OCCUPANCY
C
CERT. NO.
50699
N.C .N O ITAROP
R
O
C
L
A
RUTCETIHRAC
DE
E
R
G
T
S
I
ER
JB A P.A.
R
LAEIG H ,N .C .
,
ANILORACHT
R
O
N
I
C .N .H ,GELAR
REGI S T E R E AR
C
H
I
T
E
CT
D
7475
J
EN N I F E R R .
A
M
S
T
E
R
PROJECT NUMBER
SHEET NUMBER
SHEET TITLE
DRAWN BY
ISSUE DATE
REVISIONS
PRELIMINARY
CHECKED BY
BJ
A
C
,
P
A
D O N O T S C A LE D R A W I N G S
N O T F O R C O N S T R U C T I O N
811 W. Hargett St., Raleigh, NC 27603
919.833.8818 v 919.833.6898 f www.bjac.com
c
Chapel Hill, NC
27599
G002
NCSBC APPENDIX B
- BUILDING CODE
SUMMARY
University of North
Carolina at Chapel Hill
Macnider Hall 3rd
Floor Renovations
7667-01
06/18/2012